1. 某工廠負載為 1000kVA,功率因數為 0.8 滯後,若欲改善功率因數至 1.0,則需裝置多少kVAR 之電容器?
(A)200
(B)800
(C)600
(D)400。
答案:登入後查看
統計: A(2), B(6), C(19), D(3), E(0) #3467784
統計: A(2), B(6), C(19), D(3), E(0) #3467784
詳解 (共 1 筆)
#6572865
【步驟一】計算有效功率 P:
P = S × cosθ₁
= 1000 × 0.8
= 800 kW
P = S × cosθ₁
= 1000 × 0.8
= 800 kW
--------------------------------------------------
【步驟二】計算原來的無功功率 Q₁:
Q₁ = √(S² - P²)
= √(1000² - 800²)
= √(1,000,000 - 640,000)
= √360,000
= 600 kVAR
【步驟二】計算原來的無功功率 Q₁:
Q₁ = √(S² - P²)
= √(1000² - 800²)
= √(1,000,000 - 640,000)
= √360,000
= 600 kVAR
--------------------------------------------------
【步驟三】功率因數改善後,無功功率為 Q₂ = 0
【步驟三】功率因數改善後,無功功率為 Q₂ = 0
所需電容器補償容量:
Qc = Q₁ - Q₂
= 600 - 0
= 600 kVAR
Qc = Q₁ - Q₂
= 600 - 0
= 600 kVAR
0