65.某100 kVA單相變壓器,在額定電壓及負載時之鐵損爲1 kW、銅損爲1.25 kW,則運轉於0.5載、功率因數爲 0.8滯後時之效率爲多少?
(A) 86.9%
(B) 89.6%
(C) 96.8%
(D) 98.6%
答案:登入後查看
統計: A(15), B(37), C(242), D(51), E(0) #970232
統計: A(15), B(37), C(242), D(51), E(0) #970232
詳解 (共 2 筆)
#4382081
效率= 100 x 0.8 x 0.5 / 100 x 0.8 x 0.5 +1+ (1/2)^2 x 1.25 = 0.968
3
0